Section 10
Control
10.10.4
Settings
Table 260: I103CMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
10.11
IED commands for IEC 60870-5-103 I103IEDCMD
10.11.1
Functionality
I103IEDCMD is a command block in control direction with defined IED functions.
10.11.2
Function block
BLOCK
IEC10000283 V1 EN-US
Figure 174: I103IEDCMD function block
10.11.3
Signals
Table 261: I103IEDCMD Input signals
Name
BLOCK
Table 262: I103IEDCMD Output signals
Name
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
334
Unit
-
I103IEDCMD
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283-1-en.vsd
Type
Default
BOOLEAN
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
Step
Default
1
1
Description
Block of commands
Description
Information number 19, reset LEDs
Information number 23, activate setting group 1
Information number 24, activate setting group 2
Information number 25, activate setting group 3
Information number 26, activate setting group 4
1MRK 506 326-UUS B
Description
Function type (1-255)
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v1
GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1
Line distance protection REL650
Technical manual
PID-2649-SETTINGS v4
PID-2650-INPUTSIGNALS v4
PID-2650-OUTPUTSIGNALS v4