1MRK 506 326-UUS B
16.3.7
Time synchronization via IRIG-B
16.3.7.1
Identification
Function description
Time synchronization via IRIG-B
16.3.7.2
Settings
Table 502: IRIG-B Non group settings (basic)
Name
Values (Range)
TimeDomain
LocalTime
UTC
Encoding
IRIG-B
1344
1344TZ
TimeZoneAs1344
MinusTZ
PlusTZ
16.3.8
Operation principle
16.3.8.1
General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time the clock is
intended to have. The rate accuracy of a clock is normally called the clock accuracy and means how
much the error increases, that is how much the clock gains or loses time. A disciplined (trained)
clock knows its own faults and tries to compensate for them.
Design of the time system (clock synchronization)
External
synchronization
sources
Disabled
SNTP
IRIG-B
DNP
IEC60870-5-103
ANSI09000210 V1 EN-US
Figure 286: Design of time system (clock synchronization)
Line distance protection REL650
Technical manual
IEC 61850
identification
IRIG-B
Unit
Step
-
-
-
-
-
-
Time-
regulator
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Default
Description
LocalTime
Time domain
IRIG-B
Type of encoding
PlusTZ
Time zone as in 1344 standard
Time tagging and general synchronization
Commu
Events
- nication
SW- time
ANSI09000210-1-en.vsd
Section 16
Basic IED functions
GUID-0A8E1E7F-12A3-4B71-944D-BF8B38DC4F5E v2
PID-1936-SETTINGS v7
M11346-80 v2
GUID-6014BF61-0C79-44AF-B8A8-1C9C0D3A2D56 v3
Protection
and control
functions
M11346-77 v1
547