ABB Relion 650 Series Technical Manual page 425

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Name
Values (Range)
V1ZeroDb
0 - 100000
V1HiHiLim
0 - 2000000
V1HiLim
0 - 2000000
V1LowLim
0 - 2000000
V1LowLowLim
0 - 2000000
V1LimHys
0.000 - 100.000
V2ZeroDb
0 - 100000
V2HiHiLim
0 - 2000000
V2HiLim
0 - 2000000
V2LowLim
0 - 2000000
V2LowLowLim
0 - 2000000
13.4.6.5
Monitored data
Table 381: VMSQI Monitored data
Name
3V0
3V0ANGL
V1
V1ANGL
V2
V2ANGL
13.4.7
Phase-neutral voltage measurement VNMMXU
13.4.7.1
Identification
Function description
Phase-neutral voltage measurement
13.4.7.2
Function block
The available function blocks of an IED are depending on the actual hardware (TRM) and the logic
configuration made in PCM600.
Line distance protection REL650
Technical manual
Unit
Step
m%
1
V
1
V
1
V
1
V
1
%
0.001
m%
1
V
1
V
1
V
1
V
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
IEC 61850
identification
VNMMXU
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
500
Zero point clamping
96000
High High limit (physical value)
86000
High limit (physical value)
71000
Low limit (physical value)
66000
Low Low limit (physical value)
5.000
Hysteresis value in % of range and is
common for all limits
500
Zero point clamping
96000
High High limit (physical value)
86000
High limit (physical value)
71000
Low limit (physical value)
66000
Low Low limit (physical value)
Unit
Description
kV
3U0 Amplitude
deg
3U0 Angle
kV
U1 Amplitude
deg
U1 Angle
kV
U2 Amplitude
deg
U2 Angle
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
U
SYMBOL-UU V1 EN-US
Section 13
Monitoring
PID-1235-MONITOREDDATA v7
GUID-607EFE25-4C20-43AC-9259-82AAA966F22A v1
GUID-440B43E6-39FF-43A9-8E11-B45ACBCAC5CF v2
419

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents