Section 13
Monitoring
Name
Values (Range)
VLimHyst
0.000 - 100.000
IDbRepInt
1 - 300
IZeroDb
0 - 100000
IHiHiLim
0.0 - 500.0
IHiLim
0.0 - 500.0
ILowLim
0.0 - 500.0
ILowLowLim
0.0 - 500.0
ILimHyst
0.000 - 100.000
FrDbRepInt
1 - 300
FrZeroDb
0 - 100000
FrHiHiLim
0.000 - 100.000
FrHiLim
0.000 - 100.000
FrLowLim
0.000 - 100.000
FrLowLowLim
FrLimHyst
VMagComp5
VMagComp30
VMagComp100
IMagComp5
IMagComp30
IMagComp100
IAngComp5
IAngComp30
IAngComp100
408
Unit
%
Type
m%
%IB
%IB
%IB
%IB
%
Type
m%
Hz
Hz
Hz
0.000 - 100.000
Hz
0.000 - 100.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
Deg
-10.000 - 10.000
Deg
-10.000 - 10.000
Deg
© Copyright 2011 ABB Power Grids. All rights reserved
Step
Default
0.001
5.000
1
10
1
500
0.1
150.0
0.1
120.0
0.1
80.0
0.1
60.0
0.001
5.000
1
10
1
500
0.001
65.000
0.001
63.000
0.001
47.000
0.001
45.000
0.001
5.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
1MRK 506 326-UUS B
Description
Hysteresis value in % of range (common
for all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Hysteresis value in % of range (common
for all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range (common
for all limits)
Magnitude factor to calibrate voltage at
5% of Vn
Magnitude factor to calibrate voltage at
30% of Vn
Magnitude factor to calibrate voltage at
100% of Vn
Magnitude factor to calibrate current at
5% of In
Magnitude factor to calibrate current at
30% of In
Magnitude factor to calibrate current at
100% of In
Angle calibration for current at 5% of In
Angle calibration for current at 30% of In
Angle calibration for current at 100% of In