Section 13
Monitoring
13.13.2
Functionality
The accurate fault locator is an essential component to minimize the outages after a persistent
fault and/or to pin-point a weak spot on the line.
The fault locator is an impedance measuring function giving the distance to the fault as a relative
(in%) or an absolute value. The main advantage is the high accuracy achieved by compensating for
load current.
The compensation includes setting of the remote and local sources and calculation of the
distribution of fault currents from each side. This distribution of fault current, together with
recorded load (pre-fault) currents, is used to exactly calculate the fault position. The fault can be
recalculated with new source data at the actual fault to further increase the accuracy.
Especially on heavily loaded long lines (where the fault locator is most important) where the
source voltage angles can be up to 35-40 degrees apart the accuracy can be still maintained with
the advanced compensation included in fault locator.
13.13.3
Function block
PHSEL_A*
PHSEL_B*
PHSEL_C*
CALCDIST*
ANSI09000621 V1 EN-US
Figure 245: LMBRFLO function block
13.13.4
Signals
Table 415: LMBRFLO Input signals
Name
PHSEL_A
PHSEL_B
PHSEL_C
CALCDIST
472
LMBRFLO
CALCMADE
FLTDISTX
BCD_80
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1
ANSI09000621-1-en.vsd
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Phase selection phase A
Phase selection phase B
Phase selection phase C
Input signal to initiate fault distance calculation
1MRK 506 326-UUS B
M13970-3 v7
M16684-3 v5
GUID-4426B242-BE9E-4D6A-8DFF-9EB9F728A36A v1
PID-1797-INPUTSIGNALS v5
Line distance protection REL650
Technical manual