ABB Relion 650 Series Technical Manual page 395

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Table 343: B16IFCVI Output signals
Name
OUT
12.7.5
Settings
The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)
12.7.6
Monitored data
Table 344: B16IFCVI Monitored data
Name
OUT
12.7.7
Operation principle
The Boolean 16 to integer conversion with logic node representation function (B16IFCVI) will
transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx
represents a value according to the table below from 0 to 32768. This follows the general formula:
x-1
INx = 2
output OUT as a sum of the integer values of all the inputs INx that are activated. OUT is an
integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to that
integer 65535 is available on the output OUT. The B16IFCVI function is designed for receiving the
integer input from a station computer - for example, over IEC 61850. If the BLOCK input is
activated, it will freeze the logical outputs at the last value.
Values of each of the different OUTx from function block B16IFCVI for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block B16IFCVI.
Name of input
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
Table continues on next page
Line distance protection REL650
Technical manual
Type
INTEGER
Type
Values (Range)
INTEGER
where 1≤x≤16. The sum of all the values on the activated INx will be available on the
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Output value
Unit
-
-
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
Description
Output value
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
Section 12
Logic
PID-1895-OUTPUTSIGNALS v5
ABBD8E241926 v2
PID-1895-MONITOREDDATA v7
SEMOD158425-4 v3.1.1
389

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents