Remedy:
- Check ambient temperature at component installation location.
- replace the component involved.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A36211 (F, N)
Hub: Overtemperature alarm component
Message value:
%1
Message class:
Overtemperature of the electronic components (6)
Drive object:
B_INF, HUB, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature on the DRIVE-CLiQ Hub Module has exceeded the alarm threshold.
Alarm value (r2124, interpret decimal):
Actual temperature in 0.1 °C resolution.
Remedy:
- Check ambient temperature at component installation location.
- replace the component involved.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F36214 (N, A)
Hub: overvoltage fault 24 V supply
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
B_INF, HUB, VECTOR_G
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The 24 V power supply on the DRIVE-CLiQ Hub Module has exceeded the fault threshold.
Fault value (r0949, interpret decimal):
Actual operating voltage in 0.1 °C resolution
Remedy:
- check the supply voltage of the component involved.
- replace the component involved.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F36216 (N, A)
Hub: undervoltage fault 24 V supply
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
B_INF, HUB, VECTOR_G
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The 24 V power supply on the DRIVE-CLiQ Hub Module has undershot the fault threshold.
Fault value (r0949, interpret decimal):
Actual operating voltage in 0.1 °C resolution
Remedy:
- check the supply voltage of the component involved.
- replace the component involved.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE