Make the Remaining Connections

Return to Task List
For a fiber-remoted SCC EPN, see
DS1-remoted SCC EPN and associated CSUs, see
page 789.
1
Plug the 700A8 plug into the Z3A2 UPS alarm adapter.
2
Connect the alarm adapter to the UPS DB25 RS-232 serial port connector.
3
Connect the wires from the plug to the 110 cross-connect field for the AUX connector (see
42, Wire Connections,
Field for the AUX Connector,
If connecting a UPS for a DS1-remoted SCC1 EPN:
4
Plug the CSU(s) used in the A-level DS1 converter into the UPS.
Table 42: Wire Connections
700A8 Plug
UPS Alarm
Name
Pair 1:
Utility Fail Alarm
Pair 3:
UPS Fail Alarm
SI Installation and Upgrades
June 2004
Figure 304, UPS for Fiber-Remoted SCC1 EPN,
on page 787 and
Figure 306, Enlarged View of the 110 Cross-Connect
on page 790).
DEFINITY AUX Connector 110
Field
Pins
Pins
1
Connects to
1
2
2
5
3
6
4
UPS Installation for SCC1 EPN A-Carrier Cabinet
3
Utility fail wire pair
4
UPS fail wire pair
Figure 305, UPS for DS1 Remoted SCC1 EPN,
External Alarm Name
1M
Major Alarm Pair
1m Minor Alarm Pair
Task List: Install UPS
on page 788. For a
on
Table
787