Avaya MCC1 Installation And Upgrades page 383

Media gateways installation and avaya definity server si upgrades made easy
Hide thumbs Also See for MCC1:
Table of Contents

Advertisement

Task List: Connect the cabinet grounds on the J58890R DC Power Cabinet and the Single-Carrier Cabinets
5
At Cabinet A, connect a 10 AWG (#25) (2.5 mm
AWG (#25) (2.5 mm
rear of the system cabinets, follow these cables to the Main Distribution Frame (MDF), and to
terminate at the Coupled Bonding Conductor (CBC).
The Coupled Bonding Conductor (CBC) wires are installed and terminated in
Telecommunications Cabling
Figure 119: Typical AC Power and Ground Layout — Rear
1
2
3
4
7
Figure notes
1
Cabinet Stack 1 Control Cabinet A
2
Circuit Breaker
3
AC Power Receptacle
4
Cabinet Stack Single-Point Ground
Block
5
8-foot (2.5 meters) Power Cord
Return to Task List
SI Installation and Upgrades
June 2004
2
) wire must be long enough to reach the telecommunications cables at the
on page 403.
On
On
Off
Off
5
8
Install and Connect SCC1 (Single-Carrier Cabinets)
2
) wire to the single-point ground block. The 10
6
6
National Electrical Manufacturers
Association (NEMA) 5-15 or 5-20
Receptacle or Equivalent
7
6 AWG (#40) (4 mm2) Ground Wire to
Approved Ground
8
10 AWG (#25) (2.5 mm2) Wire to
Coupled Bonding Conductor
Install
r781851b CJL 030896
383