Load-Test And Verify Alarms - Avaya MCC1 Installation And Upgrades

Media gateways installation and avaya definity server si upgrades made easy
Hide thumbs Also See for MCC1:
Table of Contents

Advertisement

8
Type
add eda-external-device-alrm XXminor
9
Type XXminor in the Port field.
10
Type minor in the Alarm Type field.
11
Type UPS A in the Alt Name field.
12
Type A Level UPS is on Electronic Bypass in the Description field.
13
Enter data in the remaining fields based on your installation requirements.
14
When done, press Enter.
Return to Task List

Load-test and Verify Alarms

Return to Task List
CAUTION:
Do not remove or unplug the input cord when the UPS is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
15
With the Avaya Media Gateway on the UPS, find the (dedicated) circuit breaker that feeds power
to the receptacle that the UPS is plugged into.
16
Turn the breaker off. At that time, the UPS sounds an alarm, and the RED LED (ON BATTERY)
and 3 GREEN LEDs (L1, L2, and L3) above the GREEN LED (OUTPUT) light up.
17
If the EDA is turned on, type
Verify that the test fails.
18
If the EDA is turned off, type
19
Type your requirements in the various fields of the Alarm Report, then press Enter.
20
Verify that you have a major alarm on EXT-DEV for Port XXmajor. You do not need to verify a
minor alarm (UPS on Electronic Bypass).
21
If a U.S. installation, call the Product Performance and Analysis organization on 800-242-2121,
press 0 (zero), and enter extension 85284. Verify that the EXT-DEV XX major alarm was reported
to them.
22
Ask the Product Performance and Analysis organization to establish a data base for the
installation location (IL). This defines the major and minor external alarms.
The Product Performance and Analysis organization enters the major alarm on EXT DEV XX as
"Loss of Commercial Power, UPS on Battery" and the minor alarm on EXT DEV XX is "UPS is
on Electronic Bypass."
Return to Task List
SI Installation and Upgrades
June 2004
UPS Installation for SCC1 EPN A-Carrier Cabinet
and press Enter.
test eda-external-device-alrm physical XXmajor
and press Enter.
display alarms
Task List: Install UPS
and press Enter.