Avaya MCC1 Installation And Upgrades page 432

Media gateways installation and avaya definity server si upgrades made easy
Hide thumbs Also See for MCC1:
Table of Contents

Advertisement

Install Telecommunications Cabling
Patch Cord/Jumper Installation and Administration
Connect Control Carrier Outputs Cable
Return to Task List
1
Plug the connector cable in the AUX connector on the rear of the Control Carrier.
2
Route the connector cable through the cable slack manager to the assigned 110-type terminal
block in the yellow field of the trunk/auxiliary field.
Connect Trunk Pairs Using Concentrator Cables
Return to Task List
Figure 155, Connect Trunk Pairs Using Concentrator Cables,
the cabinet with concentrator cables. To install the cables:
1
Connect B25A cables between the network interface and sneak fuse panels.
2
Connect A25D cables from the sneak fuse panels to the 110-type terminal block connectors in the
green field.
3
Connect patch cords/jumper wires from the terminal block in the green field to the associated
terminal block in the purple field.
4
Connect the single-fingered end of the concentrator cables to the 110-type terminal block
connectors in the purple field in Step 3.
5
Connect the other end (2/3-fingered end) of the concentrator cables to the appropriate carrier
slots. Equipped carrier slots are identified on the CSD. Mark the nomenclature strips above the
carriers to identify the slots.
6
Label connectors on each end of the cables that connect to the cabinet.
7
Route the cables down the sides of the cabinet and store the excess cable slack in the cable slack
manager as previously described.
432
on page 433 shows trunk pairs connected to
SI Installation and Upgrades
June 2004

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scc1

Table of Contents