Test the System
This section provides tests to:
•
review the status of the system
•
test the tone-clock, TDM bus, and duplication link in the Processor Port Network (PPN)
•
test the expansion interfaces, tone-clock(s), TDM buses, and duplication in the Expansion Port
Networks (EPNs).
These tests verify the Time Division Multiplexing (TDM) cables, terminators, and the Inter-Cabinet
Cables (ICC). If a FAIL Result code is seen or other problems are indicated, check these cables. If
problems persist, refer to the Maintenance for Avaya DEFINITY® Server SI (555-233-123)
documentation.
See
LED Indicators
circuit packs.
NOTE:
Circuit pack positions are usually given by cabinet, carrier, and slot. They may also be
given by port. The term "cabinet" refers either to a stack of SCC1 (Single-Carrier
Cabinets) or to an MCC1 (Multi-Carrier Cabinet) making up one port network. A port
network is defined as a group of cabinets connected together with one TDM bus.
Task List: Test the System
CAUTION:
To prevent unnecessary trouble tickets, do not enable the system alarms (Alarm
Origination feature) until all installation and administration procedures are completed.