Avaya MCC1 Installation And Upgrades page 445

Media gateways installation and avaya definity server si upgrades made easy
Hide thumbs Also See for MCC1:
Table of Contents

Advertisement

Install Coupled Bonding Conductor
Return to Task List
The
Figure 165, Coupled Bonding Conductor,
block and runs adjacent to pairs in an associated telecommunications cable. The mutual coupling between
the bonding conductor and the pairs reduces potential differences in terminating equipment.
1
Cut a 10 AWG (#25) (2.5 mm
block or DC power cabinet Ground Discharge Bar to the MDF CBC block.
2
Connect one end of the 10 AWG (#25) (2.5 mm
Ground Discharge Bar).
3
Route the wire next to the 25-pair cables connecting to the trunk/auxiliary (purple) field.
4
Tie wrap the 10 AWG (#25) (2.5 mm
5
Connect the 10 AWG (#25) (2.5 mm
6
Repeat the above steps for each CBC ground wire installed.
SI Installation and Upgrades
June 2004
Patch Cord/Jumper Installation and Administration
on page 446 (CBC) connects to the single-point ground
2
) wire long enough to reach from the system's single-point ground
2
) wire to the single-point ground block (or
2
) wire to the 25-pair cables.
2
) wire to the MDF CBC ground block.
Install Telecommunications Cabling
445

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scc1

Table of Contents