Download Print this page

Siemens SINAMICS DCM Manual page 651

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Maintenance
11.1 Upgrading software releases
11.1
Upgrading software releases
This chapter describes how you can upgrade a drive – including STARTER project – from
one software version to a higher software version (e.g. V1.1 to V1.2).
Basic information
The following steps are necessary:
● Upgrade the device software
– Step 1: Backup the configuration
– Step 2: Update the drive software (incl. the peripherals)
– Step 3: Update the STARTER project
– Step 4: Load into the target system, RAM to ROM
● Upgrade the DCC technology option (optional)
– Step 5: Update the DCC technology option (DCBLIB) and the DCC charts
– Step 6: Load into the target system, RAM to ROM
Note
A memory card is required to update the software (see Chapter "Ordering data for options
and accessories").
When updating the software, always proceed as follows:
1. Software update of the drive
– Insert the memory, then switch the electronic power supply OFF and ON again. The
– Switch the electronic power supply OFF and ON again. The device firmware just
– If only a CBE20 is connected, there is no indication after the second OFF and ON that
2. Update the STARTER project
3. Load the converted STARTER project to the drive (load to the target device)
652
device firmware is now installed.
installed now powers up.
If neither a CBE20 nor DRIVE-CLIQ components are available, the drive is ready for
operation.
However, if a CBE20 or DRIVE-CLIQ components or both are available, the firmware
of these components is updated during the power-up of the device firmware. At the
end of the power-up of the device firmware, the DRIVE-CLiQ components indicate that
a restart is required through flashing red LEDs. Alarm A1006 also appears. Switch the
electronic power supply OFF and ON again a third time.
the CBE20 also requires a restart so that the CBE20 firmware installed in the above
step is also started. However, a third OFF and ON of the electronic power supply is
also required in this case.