Operation
9.3 Controlling via the AOP30 operator panel
AOP setpoint ramp-down time (factory setting: 30 s)
Defines the speed at which the setpoint specified by the AOP is decreased when the "-" key
is pressed
AOP starting setpoint (factory setting: 0.000 rpm)
The AOP starting setpoint is the speed setpoint which is active when the drive is switched on
(with the "ON" key on the AOP30); the "Save setpoint" system setting must be set to "No" for
this purpose (see also the description of the "Save AOP setpoint" system setting).
Note
The internal drive ramp-function generator is always active.
9.3.7.7
Inhibiting AOP LOCAL mode
Settings: Menu – Commissioning/Service – AOP settings – Control settings
Inhibit AOP LOCAL mode (factory setting: No)
● Yes: Deactivates the "Control via operator panel" function, thereby disabling the
LOCAL/REMOTE key.
● No: Activates the LOCAL/REMOTE key.
Note
LOCAL functionality can also be inhibited on the drive by means of the p0806 parameter
(BI: Inhibit master control).
9.3.7.8
Acknowledging errors via the AOP
Settings: Menu – Commissioning/Service – AOP settings – Control settings
Acknowledge error from the AOP (factory setting: Yes)
● Yes: Errors can be acknowledged via the AOP.
● No: Errors cannot be acknowledged via the AOP.
9.3.7.9
Timeout monitoring
In "LOCAL" mode or if "OFF in REMOTE" is active, the drive is shut down after 1 s. if the
data cable between the AOP and drive is disconnected.
370
Operating Instructions, 02.2015, A5E34763375/RS-AA/001