7.3.8
Protective conductor connection and shield support
It is always advisable to shield the digital I/O wiring.
The following diagrams show typical Weidmüller shield connection terminals for the shield
supports.
Figure 7-17
NOTICE
Damage or faulty operation due to incorrect shielding and impermissible cable lengths
If the correct shielding procedures and the permissible cable lengths are not observed, the
machine can be damaged or may malfunction.
• Only use shielded cables.
• Do not exceed the cable lengths stated in the technical data.
Note
Only use screws with a permissible mounting depth of 4 - 6 mm.
The TM15 enclosure is connected to the ground terminal of the module supply (terminal
X524). If the ground terminal is actually grounded, then the enclosure is also grounded. An
additional ground connection using the M4 screw is especially necessary if high equipotential
bonding currents can flow (e.g. through the cable shield).
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Protective conductor connection M4 / 1.8 Nm
Weidmüller
Type: KLBÜ CO 1
Order no. 1753311001
Shield supports and protective conductor connection
ac.maher.co.ir
Additional system components
7.3 Terminal Module TM15
223