For certain user actions (e.g. restore factory setting) a two-digit number is displayed on the
BOP20. This number provides information about the drive state. The significance of these
numbers is provided in Appendix B.
Information on the keys
Table 9- 6
Keys
Key
Name
ON
Power up the drives for which the "ON/OFF1" command should come from the BOP.
Binector output r0019.0 is set using this key.
OFF
Power down the drives for which the "ON/OFF1", "OFF2", or "OFF3" commands should come
from the BOP.
Binector outputs r0019.0, .1 and .2 are simultaneously reset when this key is pressed. After the
key has been released, binector outputs r0019.1 and .2 are again set to a "1" signal.
Note:
Whether these keys are active can be defined by assigning appropriate BICO parameters (e.g. it
is possible to use these keys to control all of the existing drives at the same time).
Functions
The meaning of these keys depends on the current display.
Note:
The effectiveness of this key to acknowledge faults can be defined via BICO parameterization.
Parameters The meaning of these keys depends on the current display.
If this key is pressed for 3 s, the "Copy RAM to ROM" function is executed. The "S" displayed on
the BOP disappears.
Increase
The keys depend on the current display and are used to either increase or decrease values.
Decrease
BOP20 functions
Table 9- 7
Functions
Name
Backlighting
Switch active drive
Units
Access level
Parameter filter
Select status display
User parameter list
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
9.2 Parameterizing using the BOP20 (Basic Operator Panel 20)
The backlighting can be set using p0007 in such a way that it switches itself off automatically
after the set time if no actions are carried out.
From the BOP perspective, the active drive is defined using p0008 or using the keys "FN" and
"Arrow up".
The units are not displayed on the BOP.
The access level for the BOP is defined using p0003.
The higher the access level, the more parameters can be selected using the BOP.
Using the parameter filter in p0004, the available parameters can be filtered according to their
particular function.
Actual values and setpoints are displayed on the status display.
The status display can be set via p0006.
Parameters can be selected for access using the user parameter list in p0013.
ac.maher.co.ir
Meaning
Description
Operation
345