Additional system components
7.4 Terminal Module TM31
7.4.3.4
X521 analog inputs
Table 7- 29
X521 terminal strip
Terminal
1
2
3
4
5
6
7
8
AI: Analog inputs; P10/N10: Auxiliary voltage; M: Ground reference
1)
NOTICE
If more than ±35 mA flows through the analog current input, then the component could be
destroyed.
Permissible input voltage ±30 V (destruction limit).
Permissible common-mode voltage ±10 V, increased faults if exceeded.
Permissible back-EMF at the auxiliary voltage outputs ±15 V.
Note
The power supply for the analog inputs can be taken internally or from an external power
supply unit
232
Designation
1)
AI 0+
AI 0-
AI 1+
AI 1-
P10
M
N10
M
ac.maher.co.ir
Technical specifications
The analog inputs can be toggled between current and
voltage input using switches S5.0 and S5.1.
Voltage: -10 to 10 V; R
= 100 kΩ
i
Resolution: 11 bits + sign
Current: R
= 250 Ω
i
Resolution: 10 bits + sign
Auxiliary voltage:
P10 = 10 V
N10 = -10 V
Continuous short-circuit proof