Reaction:
Measured air intake temperature (r52050[1] or r50013[1])
• Is greater than the alarm threshold
• Is higher than the fault threshold
• Is greater than 115° C
• Is less than -25° C
Use of the SINAMICS DCM in a SINAMICS DCM Cabinet drive cabinet with option L99
Option L99 provides the same functionality as option L15.
Devices with software version as of 1.4:
Alarm A60082 is output if the drive performs an automatic derating as a result of the
measured air intake temperature. The response threshold for this alarm can be configured
with p50066.
The description for option L99 can be found in the operating instructions for the SINAMICS
DCM Cabinet.
Note
For devices with option L15, p50066 has no effect and A60082 is not available.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
10.23 Sensor for the ambient and/or air intake temperature
ac.maher.co.ir
Descriptions of functions
Alarm A60080
Fault F60067
Fault F60096 with fault value 2 (i.e. the
temperature sensor is short-circuited)
Fault F60096 with fault value 1 (i.e. the
temperature sensor is interrupted)
557