10.5.3
Drive control with PROFINET
PROFINET interfaces
The CBE20 option module can be inserted in the option slot of a CUD. The CBE20 is a
PROFINET switch with four ports.
Note
Ring topology
When connecting the ports, it must be ensured that for standard applications a ring topology
is not created. Additional information on ring topologies can be found in Chapter Media
redundancy (Page 475).
References
● The integration of a SINAMICS Control Unit in a PROFINET IO system is described in
detail in System Manual "SIMOTION SCOUT Communication".
● For an example of how to link a Control Unit to a SIMATIC S7 via PROFINET IO, please
refer to the FAQ "PROFINET IO communication between an S7-CPU and SINAMICS
S120" on the Internet.
● For a description of the CBE20 and how you can use it in the drive, see Chapter Option
Board: Communication Board Ethernet CBE20 (Page 190).
Telegrams
PROFIdrive telegrams are available for implementing cyclic communication via PROFINET
IO (see Chapter "Communication according to PROFIdrive", cyclic communication).
DCP flashing
This function checks the correct assignment to a module and its interfaces.
1. In HW Config or the STEP 7 Manager, select the menu item "Target system" > Ethernet >
Edit Ethernet node".
The "Edit Ethernet Node" dialog box opens.
2. Click the "Browse" button.
The "Browse Network" dialog box opens and displays the connected nodes.
3. Select the CUD with inserted CBE20 as node.
The "DCP flashing" function is then activated via the "Flash" button.
The "DCP flashing" function is activated on the RDY LED (READY LED 2 Hz, green/orange
or red/orange) on the CUD.
The LED will continue to flash as long as the dialog is open. When the dialog is closed, the
LED will go out automatically. The function is available as of STEP 7 V5.3 SP1 via Ethernet.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
ac.maher.co.ir
Descriptions of functions
10.5 Communication via PROFINET IO
473