8.6
Commissioning optional additional modules
Additional modules can be integrated through DRIVE-CLiQ (TM15, TM31, TM150, SMC30)
or OMI slot (CBE20).
The components must be logged in to the software during a first commissioning.
That can be done:
● Offline by inserting the components into the project in STARTER and loading the project
into the drive or
● By adding the components through the parameter assignments on BOP20 / AOP30
8.6.1
Terminal Modules (TM31, TM15, TM150)
8.6.1.1
Commissioning with STARTER
Requirement
The project must be consistent with the drive before adding the TMxx. Load to the PG and
then go offline.
An I/O component can only be inserted in the offline state.
Figure 8-37
● Double-click "Insert input/output component".
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Inserting I/O component (1)
ac.maher.co.ir
8.6 Commissioning optional additional modules
Commissioning
305