Connecting
6.6 Line reactors
Table 6- 7
3-phase line reactors, rated voltage = 690 VAC, uk = 4%
Article number
Rated current Inductance
6RX1800-4KK00
598 A AC
6RX1800-4KK01
631 A AC
6RX1800-4KK02
789 A AC
6RX1800-4KK03
830 A AC
6RX1800-4KK04
1245 A AC
6RX1800-4KK05
1577 A AC
6RX1800-4KK06
1660 A AC
6RX1800-4KK07
2158 A AC
Table 6- 8
3-phase line reactors, rated voltage = 830/950 VAC, uk = 4%
Article number
Rated current Inductance
830 V:
6RX1800-4LK00
789 A AC
6RX1800-4LK01
1245 A AC
6RX1800-4LK02
1577 A AC
6RX1800-4LK03
1826 A AC
950 V:
6RX1800-4MK00 1826 A AC
Table 6- 9
1-phase line reactors, rated voltage = 400 VAC, uk = 4%
Article number
Rated current
6RX1800-4DE00
3 A AC
6RX1800-4DE01
5 A AC
6RX1800-4DE02
10 A AC
6RX1800-4DE03
15 A AC
6RX1800-4DE04
25 A AC
6RX1800-4DE05
30 A AC
6RX1800-4DE06
40 A AC
6RX1800-4DE07
85 A AC
Connections:
3-phase reactors with rated current ≤85 A:
3-phase reactors with rated current >85 A:
1-phase reactors with rated current ≤30 A:
1-phase reactors with rated current >30 A:
148
Copper
Total
losses
losses
0.085 mH
388.2 W 562.1 W
0.080 mH
402.0 W 586.4 W
0.064 mH
362.7 W 564.6 W
0.061 mH
350.7 W 561.4 W
0.041 mH
505.2 W 845.7 W
0.032 mH
716.8 W 1093.8 W
0.031 mH
596.0 W 1011.8 W
0.024 mH
484.8 W 1185.6 W
Copper
Total
losses
losses
0.077 mH
312.0 W 532.1 W
0.049 mH
692.4 W 1061.9 W
0.039 mH
479.4 W 1059.6 W
0.033 mH
585.6 W 1269.0 W
0.038 mH
534.9 W 1303.5 W
Inductance
16.977 mH
10.186 mH
5.093 mH
3.395 mH
2.037 mH
1.698 mH
1.273 mH
0.599 mH
ac.maher.co.ir
SCCR
Weight
55 kA (200 ms)
108.9 kg
75 kA (200 ms)
113.3 kg
75 kA (200 ms)
141.9 kg
75 kA (200 ms)
153.4 kg
75 kA (200 ms)
169.7 kg
75 kA (200 ms)
226.1 kg
75 kA (200 ms)
257.2 kg
75 kA (200 ms)
360.2 kg
SCCR
Weight
75 kA (200 ms)
205.2 kg
75 kA (200 ms)
222.4 kg
75 kA (200 ms)
308.5 kg
75 kA (200 ms)
372.5 kg
75 kA (200 ms)
399.7 kg
Weight
0.7 kg
1.5 kg
2.0 kg
2.3 kg
3.0 kg
3.8 kg
5.2 kg
9.6 kg
Terminal blocks
Connecting lugs
Terminal blocks
Connecting lugs
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Rated insulation
voltage
1000 V
1000 V
1000 V
1000 V
1000 V
1000 V
1000 V
1000 V
Rated insulation
voltage
1000 V
1000 V
1000 V
1000 V
1000 V
Rated insulation volt-
age
600 V
600 V
600 V
600 V
600 V
600 V
600 V
600 V

Advertisement

loading