Download Print this page

Siemens SINAMICS DCM Manual page 285

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Commissioning
8.4 Commissioning with the STARTER commissioning tool
Adapting unit data and entering motor data
Figure 8-20
⇒ Adapt the rated armature DC current for the unit by making a setting at p50076[0] (in %) or
p50067 if:
Maximum armature current < 0.5 × rated armature DC current for the unit
⇒ Adapt the rated armature DC current field for the unit by making a setting at p50076[1]
(in %) if:
Maximum field current < 0.5 × rated field DC current for the unit
⇒ Enter the actual supply voltage for the unit p50078
⇒ Enter the motor rating data according to the motor rating plate here.
NOTICE
The data are very important to protect against overloading and must be entered correctly.
⇒ Click Continue >