〈7.3〉Ramp-function generator
p50303[D]
p50304[D]
p50305[D]
p50306[D]
〈8〉Complete quick commissioning
Set p3900 = 3.
This triggers the calculation of the motor data (Ra, La, Lf) as well as the calculation of the
controller parameters resulting from the data that was entered in the previous steps.
p3900 is then reset to 0 and quick commissioning is ended, i.e. p0010 is reset to 0.
〈9〉Execute optimization runs
Perform the optimization runs one after the other:
p50051 = 23
p50051 = 24
p50051 = 25
p50051 = 26
p50051 = 27
p50051 = 28
p50051 = 29
See Chapter "Drive optimization" for more details
If an optimization run is not carried out, the motor control uses the motor characteristic
values calculated from the rating plate data rather than the measured values.
WARNING
During optimization runs, the drive initiates movements of the motor shaft that can reach
the maximum motor speed. The EMERGENCY OFF functions must function at the
commissioning.
To protect man and machines, the relevant safety regulations must be observed.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
8.2 Commissioning using the BOP20 operator panel
Ramp-up time 1 (in seconds)
Ramp-down time 1 (in seconds)
Initial rounding 1 (in seconds)
Final rounding 1 (in seconds)
Optimization of the armature current control for induction load
Optimization of the field current control
Optimization of the armature current control
Optimization of the speed control
Optimization of the EMF control (incl. field characteristic recording)
Recording of the friction characteristic
Optimization of the speed control for drives with a mechanical system capa-
ble of oscillation