Download Print this page

Siemens SINAMICS DCM Manual page 330

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

9.1.2.1
Function diagrams and parameters
Function diagrams (see the SINAMICS DCM List Manual)
● 8560 Command data sets (CDS)
● 8565 Drive data sets (DDS)
● 8570 Encoder data sets (EDS)
Overview of important parameters (refer to the SINAMICS DCM List Manual)
Adjustable parameters
● p0140 Encoder data sets (EDS) number
● p0170 Command data sets (CDS) number
● p0180 Drive data sets (DDS) number
● p0187 Encoder 1 encoder data set number
● p0188 Encoder 2 encoder data set number
● p0809 Copy command data set (CDS)
● p0810 BI: Command data set CDS bit 0
● p0819[0...2] Copy drive data set DDS
● p0820 BI: Drive data set selection DDS, bit 0
● p0821 BI: Drive data set selection DDS, bit 1
9.1.2.2
Using data sets
Copying a command data set
Set parameter p0809 as follows:
1. p0809[0] = Number of the command data set to be copied (source)
2. p0809[1] = Number of the command data to which the data is to be copied (target)
3. p0809[2] = 1
Starts copying.
Copying is finished when p0809[2] = 0.
Copying a drive data set
Set parameter p0819 as follows:
1. p0819[0] = Number of the drive data set to be copied (source)
2. p0819[1] = Number of the drive data set to which the data is to be copied (target)
3. p0819[2] = 1
Starts copying.
Copying is finished when p0819[2] = 0.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
ac.maher.co.ir
Operation
9.1 Basic information