Operation
9.1 Basic information
Using the memory card for series commissioning
The memory card can also be used for series commissioning of several devices with the
same parameter assignment.
Procedure:
● Completely commission a "sample" drive. As soon as all of the parameters have been
correctly set, carry out "RAM to ROM".
● Switch-off the system and insert a memory card into the CUD. Switch on the system.
● The parameter assignment is saved on the memory card. If DCC charts are activated in
the system, then these as well as the DCC library are also saved on the memory card.
● Remove the card.
● Insert the card into a CUD that is switched-off and has still not been parameterized.
Switch on the system (POWER ON).
● When powering up, the parameter assignment is transferred into the CUD and copied into
the ROM as well as into the RAM. If DCC charts and the DCC library were saved on the
memory card, then these are also copied.
● The card can be removed once the system has powered-up. The CUD that was still not
parameterized now has the same parameter assignment as the original "sample" drive.
Note
The MLFB of the device from which the parameter data set originated is also saved in a
parameter data set. If the parameter data set is loaded into a device with another MLFB
(POWER ON with the memory card inserted), then the device signals an inconsistent
topology (power-up stops with display "33" on the BOP, fault A1420 is output). This occurs, if
e.g. a parameter set that was generated from a 30 A device is loaded into a 60 A device. In
this state, the user can accept the parameter set by setting p9906 to 3. The system
continues to power up.
The same procedure also applies if a parameter data set from a standard CUD is loaded into
an Advanced-CUD - or vice versa. The power-up procedure stops with display "33" on the
BOP; the parameter set is accepted using p9906=3 and the system continues to power up.
Important parameters
p0977:
p0802:
p0803:
p0804:
338
Save all parameters (for more information, see the SINAMICS DCM List Manual).
Data transfer of parameters [0,10,11,12], memory card as source or target
Data transfer of parameters [0...100], non-volatile device memory as source or
target
Start of parameter data transfer and specification of transfer direction:
p0804=1:
Transfer from the memory card to non-volatile device memory
p0804=2:
Transfer from non-volatile device memory to memory card