Siemens SINAMICS MV Function Manual

Medium voltage converters, two-channel firing pulse inhibit

Advertisement

Quick Links

Function Manual
Medium voltage converters
SINAMICS MV
Two-channel firing pulse inhibit
Edition
07/2021
www.siemens.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS MV

  • Page 1 Function Manual Medium voltage converters SINAMICS MV Two-channel firing pulse inhibit Edition 07/2021 www.siemens.com...
  • Page 3 Introduction Safety instructions Description Preparing for use SINAMICS Two-channel firing pulse inhibit Operation Wiring Function Manual 07/2021 A5E51227986A...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Introduction ............................5 About these instructions ...................... 5 Safety instructions ..........................7 Description............................. 9 Structure ..........................9 Function features....................... 11 Functions........................... 12 3.3.1 Switching sequences from the perspective of the system operator ........12 3.3.1.1 Activating and deactivating the firing pulse inhibit.............. 13 3.3.1.2 Deactivating the firing pulse inhibit and restarting..............
  • Page 6 Table of contents Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...
  • Page 7: Introduction

    Introduction • The function is NOT a Safe Torque Off (STO) function. • A risk analysis is not available. • STO functionality can only be implemented on the system side in conjunction with additional measures, and must be certified by a third party. •...
  • Page 8 Introduction 1.1 About these instructions Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...
  • Page 9: Safety Instructions

    Safety instructions Risk of death resulting from failure to observe the safety instructions and residual risks If you fail to heed and comply with the safety instructions and residual risks in the associated converter documentation, accidents can occur. This can result in severe injury or death. •...
  • Page 10 Safety instructions with a very low probability, the machine builder (OEM) must carefully check as to whether additional measures are required. Incorrect handling when the motor suddenly moves can result in death, serious injury or substantial material damage. • Adopt suitable protective measures to ensure that personnel is not endangered by the motor jerking into motion from standstill.
  • Page 11: Description

    Description When the "Two-channel firing pulse inhibit" function is selected, the following points apply: • The optical pulse transmission to the PSA to control the firing pulses on the thyristor gating module is switched off. • The Motor Module and the motor are not electrically isolated. Note Active loads Using the function, drive systems with active loads cannot be protected against restarting...
  • Page 12 PSA ground potential is at the ground potential of the converter housing. The components of the two-channel firing pulse inhibit are supplied with the same voltage. ③ Siemens 3SK1122-2CB4x safety relay (included in the scope of delivery of the option) Terminal Connection...
  • Page 13: Function Features

    Description 3.2 Function features ④ Power Stack Adapter (part of the basic device, not part of the option) The principle of the firing pulse interruption (inhibit) has a two-channel structure. The power supply for the diode light emitters and also the outputs of the diode light emitter drivers can be interrupted. ⑤...
  • Page 14: Functions

    Description 3.3 Functions Standard monitoring mechanisms Note Note for system integrators These standard monitoring mechanisms are implemented in the converter. Within the scope of a system acceptance test, check and document the correct principle of operation in combination with external components. •...
  • Page 15: Activating And Deactivating The Firing Pulse Inhibit

    Description 3.3 Functions 3.3.1.1 Activating and deactivating the firing pulse inhibit Selecting the firing pulse inhibit Figure 3-2 Activating and deactivating the firing pulse inhibit Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...
  • Page 16: Deactivating The Firing Pulse Inhibit And Restarting

    Description 3.3 Functions 3.3.1.2 Deactivating the firing pulse inhibit and restarting Deselecting the firing pulse inhibit Figure 3-3 Deactivating and restarting the drive Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...
  • Page 17: Preparing For Use

    Cable type • Shielded cable, Sabix D345 4x2x0.5mm² • Capacitance per unit length: 30 nF/km • SAB Bröckskes, Siemens article number 1010084 Cable length As a result of possible capacitances that may occur due to the cable installation, we recommend limiting the cable length as follows: •...
  • Page 18 Preparing for use 4.1 Wiring for cable lengths exceeding 30 m Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...
  • Page 19: Operation

    Operation It makes sense and we recommend that the drive is shut down before you activate the "Two- channel firing pulse inhibit" function. • You must manually shutdown the drive if you activate the firing pulse inhibit using a mushroom pushbutton. •...
  • Page 20 Operation Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...
  • Page 21: Wiring

    Wiring Wiring overview Pulse inhibit shutdown/activate Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...
  • Page 22: Checking The Wiring When The Function Is Retrofitted

    Wiring A.2 Checking the wiring when the function is retrofitted Checking the wiring when the function is retrofitted A.2.1 Wiring to the tripping device Requirements • The wiring to the upstream tripping device must be implemented through two channels using potential-free contacts. •...
  • Page 23: Wiring To The Psas In The Power Unit

    Wiring A.2 Checking the wiring when the function is retrofitted A.2.2 Wiring to the PSAs in the power unit 1. Initiate an external firing pulse inhibit using the connected trigger element. LED "2/OUT" flashes green/yellow. After the set delay time t = 0.5 s has elapsed, the safety relay LEDs indicate state "Device ready for operation, all outputs inactive".
  • Page 24 Wiring A.2 Checking the wiring when the function is retrofitted Two-channel firing pulse inhibit Function Manual, 07/2021, A5E51227986A...