Activating the diagnostics function
The diagnostics function is activated or deactivated via the parameterization of the relevant
configuration tool (HW Config, TIA Portal, etc.).
Figure 10-33 Activation of PROFIBUS
The following parameter assignments are possible:
Setting
Inactive
PROFIdrive error classes
When establishing the communication between SINAMICS and a master/controller, the
activated diagnostics mode of this master/controller is first transferred to the drive. With
activated diagnostics, SINAMICS first transfers all pending messages to the
master/controller.
Messages
The following PROFIBUS error texts can be displayed:
Line faulted
A line supply fault has occurred (phase failure, voltage level, etc.). Check the line supply and
fuses. Check the supply voltage. Check the wiring.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Code for parameter assignment
0
1
ac.maher.co.ir
Descriptions of functions
10.4 Communication via PROFIBUS DP
459