Siemens SINAMICS DCM Manual page 394

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Bit
Meaning
2
Operation enabled
3
Fault active
4
Coasting down not active
(OFF2 inactive)
5
Quick stop not active
(OFF3 inactive)
6
Switching on inhibited active
7
Alarm active
8
Speed setpoint/actual value
deviation in tolerance
9
Control request
"1" is always present
10
n setpoint reached or exceeded
Note:
The message is parameterized as follows: p50373 (threshold value), p50374 (hysteresis)
See FP8020 and FP2537
11
I or M limit not reached (when
p0922 = 1 or 352)
I or M limit not reached (when
p0922 = 20)
12
Holding brake released
(when p0922 = 1 or 352)
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Explanation
1
Operation enabled
Enable electronics and pulses, then ramp up to active
setpoint
0
Operation disabled
1
Fault active
The drive is faulty and, therefore, out of service. The
drive switches to "switching on inhibited" once the fault
has been acknowledged and the cause has been reme-
died. The active faults are stored in the fault buffer.
0
No fault active
There are no faults in the fault buffer.
1
Coasting down (OFF2) not active
0
Coasting down active (OFF2)
An OFF2 command is active.
1
Quick stop (OFF3) not active
0
Quick stop active (OFF3)
An OFF3 command is active.
1
Switching on inhibited
Switching back on is only possible by means of OFF1
and then ON.
0
No switching on inhibited
Switching on is possible.
1
Alarm active
The drive is operational again. No acknowledgement
necessary.
The active alarms are stored in the alarm buffer.
0
No alarm active
No alarms in the alarm buffer.
1
Setpoint/actual value monitoring in tolerance band
Actual value within tolerance band; dynamic overshoot
or undershoot permitted for t < tmax, tmax can be pa-
rameterized. See FP8020 and FP2534
0
Setpoint/actual value monitoring not within tolerance
band
1
The automation system is requested to assume control.
0
Control is only possible at the unit itself
1
n setpoint reached or exceeded
0
n setpoint not reached
1
I or M limit not reached
0
I or M limit reached or exceeded
1
I or M limit not reached
0
I or M limit reached or exceeded
1
Holding brake is released
0
Holding brake is closed
ac.maher.co.ir
Descriptions of functions
10.3 Communication according to PROFIdrive
Parameter
BO: r0899.2
BO: r2139.3
BO: r0899.4
BO: r0899.5
BO: r0899.6
BO: r2139.7
BO: r2197.7
BO: r0899.9
BO: r2199.1
BO: r1407.7
(inverted)
BO: 0056.13
(inverted)
BO: r0899.12
395