Descriptions of functions
10.3 Communication according to PROFIdrive
● Resolution: Encoder pulses ∙ 2n
n: Fine resolution, no. of bits for internal multiplication
Figure 10-8
● Encoder lines of incremental encoder
– For encoders with sin/cos 1Vpp:
Error code in Gn_XIST2
Table 10- 19 Error code in Gn_XIST2
n_XIST2
Meaning
1
Encoder fault
2
Zero mark monitoring
3
Abort parking sensor
4
Abort find reference mark
5
Abort retrieve reference
value
6
Abort flying measurement •
406
Subdivision and settings for Gx_XIST2
Encoder lines = no. of sinusoidal signal periods
Possible causes / description
One or more existing encoder faults.
Detailed information in accordance with drive messages.
Parking drive object already selected.
A fault exists (Gn_ZSW.15 = 1)
Encoder has no zero mark (reference mark)
Reference mark 2, 3 or 4 is requested
Switchover to "Flying measurement" during search for reference mark
Command "Read value x" set during search for reference mark
Inconsistent position measured value with distance-coded reference marks.
More than four values requested
No value requested
Requested value not available
No probe configured p0488, p0489
Switch over to "reference mark search" during flying measurement
Command "Read value x" set during flying measurement