Operation
9.1 Basic information
Uncommissioned data sets
Drive commissioning can be completed even if uncommissioned data sets (EDS, DDS) are
available.
Uncommissioned data sets are marked as "uncommissioned".
The attributes are displayed in STARTER or in the expert list or OPs.
Activating these data sets is not permitted and any attempt to do so will be rejected with an
error.
Assigning these data sets to a drive data set (DDS) is only possible by means of a
commissioning step (p0009 ≠ 0, p0010 ≠ 0).
Note
If there is no DDS dataset with the attribute "commissioned", the drive remains in a controller
inhibit state.
9.1.3
Drive objects
A drive object is a self-contained software function with its own parameters and potentially its
own faults and alarms. Drive objects can be provided as standard (e.g. automatic speed
control), or can be added individually or in groups times (e.g. TM31).
Properties of a drive object:
● Separate parameter space
● Separate window in STARTER
● Separate fault/alarm system
● Separate PROFIdrive telegram for process data
332
Operating Instructions, 02.2015, A5E34763375/RS-AA/001