Operation
9.1 Basic information
9.1.5.1
Binectors, connectors
Binectors, BI: Binector input, BO: Binector output
A binector is a digital (binary) signal without a unit which can assume the value 0 or 1.
Binectors are subdivided into binector inputs (signal sink) and binector outputs (signal
source).
Table 9- 3
Abbreviation
BI
BO
Connectors, CI: Connector input, CO: Connector output
A connector is a digital signal, e.g. in 32-bit format. It can be used to emulate words (16 bits),
double words (32 bits) or analog signals. Connectors are subdivided into connector inputs
(signal sink) and connector outputs (signal source).
Table 9- 4
Abbrevia-
tion
CI
CO
9.1.5.2
Interconnecting signals using BICO technology
To interconnect two signals, a BICO input parameter (signal sink) must be assigned to the
desired BICO output parameter (signal source).
The following information is required in order to interconnect a binector/connector input with
a binector/connector output:
● Binectors: Parameter number, bit number, and drive object ID
● Connectors with no index: Parameter number and drive object ID
340
Binectors
Symbol
Name
Binector input
(signal sink)
Binector output
(signal source)
Connectors
Symbol
Name
Connector input
(signal sink)
Connector output
(signal source)
ac.maher.co.ir
Description
Can be interconnected to a binector output as
source.
The number of the binector output must be
entered as a parameter value.
Can be used as a source for a binector input.
Description
Can be interconnected to a connector output as
source.
The number of the connector output must be
entered as a parameter value.
Can be used as a source for a connector input.