Commissioning
8.5 Activating function modules
Sub-function
Technology controller
Free function blocks
PROFINET interface
The function modules are activated / deactivated by setting the bits to 1 or 0.
On BOP20 or AOP30 parameter assignment is made at DO1 (CU_DC)
● p0009=2
● Correspondingly set or delete p0108[i] bits
● p0009=0
This triggers the software to reboot, therefore activating the function modules that have been
set - together with the associated parameters.
Note
Changing the parameters – The quantity structure is copied to the optional AOP30 by
"relearning" the existing parameters. This takes a few minutes.
304
p0108 bit
16
18
31
Operating Instructions, 02.2015, A5E34763375/RS-AA/001