Download Print this page

Siemens SINAMICS DCM Manual page 219

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Additional system components
7.3 Terminal Module TM15
7.3.5
Meaning of the LEDs on the Terminal Module TM15
Table 7- 22
Meanings of the LEDs on the Terminal Module TM15
LED
Color
READY
-
Off
Green
Continuous
light
Orange
Continuous
light
Red
Continuous
light
Green/re
Flashing
d
light 0.5 Hz
Flashing
light 2 Hz
Green/or
Flashing
ange
light
or
Red/oran
ge
See SINAMICS S120/S150 List Manual for the parameters to activate the recognition of components via LED
1)
Cause and rectification of faults
The following documents contain information about the cause of faults and how they can be
rectified:
SINAMICS S120 Commissioning Manual (IH1)
SINAMICS DCM List Manual
220
Status
The electronics power supply is missing or outside the per-
missible tolerance range.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated regardless of whether the correspond-
ing messages have been reconfigured.
Firmware is being downloaded.
Firmware download has been completed. The system waits
for POWER ON.
Component recognition via LED is activated
Note:
Both options depend on the LED status when component
recognition is activated.
ac.maher.co.ir
Description, cause
.
1)
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Remedy
Remove and
acknowledge the
fault.
Carry out a POWER
ON.
SINAMICS DCM DC Converter

Advertisement