8.6.2.2
Remove (with STARTER)
Note: It is only possible to remove the encoder evaluation from the project in the offline mode
● Start the drive wizard via Configuration - configure DDS
● With Continue>, go to the "Encoder" screen form, and there, deselect encoder 2
● Run through the wizard until the end
● Unplug the encoder evaluation SMC30
● Go online
● Load the project to the drive
8.6.3
PROFINET module (CBE20)
8.6.3.1
Adding online into the drive
The CBE20 is automatically detected when plugged into the slot and is integrated into the
system.
Before the module can also be addressed in the network, an IP address and device name
must be assigned; refer to the Chapter "Function descriptions", Section "PROFINET IO".
Note:
If PROFINET is to be used only as a commissioning interface but process control is through
PROFIBUS, after commissioning the CBE20 the process data interface needs to be set back
to PROFIBUS (p8839=1).