Terminal
Function
X177
27
AI 1 +
Analog input 1
28
AI 1 -
29
AI 2 +
Analog input 2
30
AI 2 -
Reference voltage
31
P10
Reference voltage ±10 V
32
N10
(output)
33, 34
M
Ground, analog
Serial interface, peer-to-peer RS485
35, 36
M
Ground, digital
37
TX+
Send cable +
38
TX-
Send cable -
39
RX+
Receive cable +
40
RX-
Receive cable -
Incremental encoder input
41
Incremental encoder supply
42
Ground, incremental encoder
43
Track 1 positive connection
44
Track 1 negative connection
45
Track 2 positive connection
46
Track 2 negative connection
47
Zero mark positive connection
48
Zero mark negative connection
Analog outputs (assignable outputs)
49
AO 0
Analog output 0
50
M
Ground, analog
51
AO 1
Analog output 1
52
M
Ground, analog
Connections for temperature sensor (motor interface 1)
53
Temp 1
54
Temp 2 (sense cable)
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Technical specifications
- Current input 0 - 20 mA; 300 Ω or 4 - 20 mA; 300 Ω
Resolution approx. 0.66 mV (±14 bits)
Common-mode controllability: ±15 V
Input type (signal type):
- Differential input ±10 V; 150 kΩ
Resolution approx. 0.66 mV (±14 bits)
Common-mode controllability: ±15 V
Note:
An external armature voltage actual value can also be connected at
this input. See function diagram 6902 in the SINAMICS DCM List
Manual.
Tolerance ±1% at 25° C
Stability 0.1% per 10° K
10 mA short-circuit proof
4-wire send cable, positive differential output
4-wire send cable, negative differential output
4-wire receive cable, positive differential output
4-wire receive cable, negative differential output
+13.7 to +15.2 V, 300 mA short-circuit proof (electronically protected)
If overload occurs: alarm A60018
Load: ≤ 5.25 mA at 15 V (without switching losses)
Pulse duty factor: 1:1
See below for data relating to cables, cable length, shield support,
input pulse levels, hysteresis, track displacement, and pulse frequen-
cy.
±10 V, max. 2 mA short-circuit proof, resolution ±15 bits
Sensor acc. to p50490 (refer to SINAMICS DCM List Manual
The cable to the temperature sensor on the motor must be shielded
ac.maher.co.ir
6.9 Assignment of terminals and connectors