Download Print this page

Siemens SINAMICS DCM Manual page 199

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Additional system components
7.2 Sensor Module Cabinet-Mounted SMC30
7.2.3.2
X500 DRIVE-CLiQ interface
Table 7- 7
DRIVE-CLiQ interface X500
Pin
1
2
3
4
5
6
7
8
A
B
Connector type: RJ45 socket; blanking plate for DRIVE-CLiQ interface included in the scope of delivery;
blanking plate (50 pieces) Article number: 6SL3066-4CA00-0AA0
7.2.3.3
X520 encoder system interface
Table 7- 8
X520 encoder system interface
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Connector type: SUB-D female, 15-pin
200
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
Reserved, do not use
M (0 V)
Signal name
Reserved
Clock
Clock*
P encoder 5 V/24 V
P encoder 5 V/24 V
P sense
M encoder (M)
Reserved
M sense
R
R*
B*
B
A*/data*
A/data
ac.maher.co.ir
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Electronics ground
Technical specifications
Do not use
SSI clock
Inverse SSI clock
Encoder supply
Sense input, encoder supply
Ground, encoder supply
Do not use
Ground for sense input
Reference signal R
Inverse reference signal R
Inverse incremental signal B
Incremental signal B
Inverted incremental signal A/inverted SSI data
Incremental signal A/SSI data
Operating Instructions, 02.2015, A5E34763375/RS-AA/001