Description
The field supply is available in the following versions:
● 1-phase, single-pair controllable two-pulse bridge circuit (B2HZ)
● 1-phase, fully-controlled two-pulse bridge circuit (B2C) (option)
The electronics (CUD) are available in the following versions:
● Standard CUD
● Advanced CUD (option)
This CUD can be expanded to include a PROFINET module (CBE20) and features two
DRIVE-CLiQ connections for connecting additional components from the SINAMICS drive
system, as well as a connector for expansion purposes (to include a second CUD).
● Additional (second) CUD (Standard or Advanced) (option)
This additional CUD can be fitted to the right of the first CUD and is used for system-
specific extension of the SINAMICS DC MASTER functions.
Additional components
● Advanced Operator Panel AOP30
The optional Advanced Operator Panel AOP30 is mounted outside of the unit - in the
control cabinet door, for example - rather than inside it.
The AOP30
– Supports commissioning by means of a commissioning wizard
– Supports the display of measured values via a graphical operation screen
– Displays a user-friendly parameter list, including text
– Features several editors for user-friendly setting and changing of parameters
– Displays lists of faults and alarms that have occurred, as well as help text concerning
– Enables "local" drive control (ON/OFF, setpoint setting, jog mode, direction reversal)
– Features three LEDs for displaying the drive state
● Additional module CBE20
The additional module CBE20 is inserted in the optional module slot of an Advanced
CUD. It enables the SINAMICS DC MASTER to participate in PROFINET network as
slave as well as to establish SINAMICS Link connections.
● DRIVE-CLiQ components
The DRIVE-CLiQ interface enables components from the SINAMICS drive system to be
connected.
The following components are supported:
– TM15 (digital inputs/outputs)
– TM31 (digital inputs/outputs, analog inputs/outputs)
– TM150 (temperature sensor inputs)
– SMC30 (incremental encoder evaluation for actual speed value acquisition)
An SMC30 and up to three TMx modules can be connected to each CUD.
38
the individual faults and alarms
ac.maher.co.ir
SINAMICS DCM DC Converter