Download Print this page

Siemens SINAMICS DCM Manual page 366

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

9.3.7
Operation via the operator panel (LOCAL mode)
You activate the control keys by switching to LOCAL mode. If the green LED in the
LOCAL/REMOTE key does not light up, the key is not active.
Note
If the "OFF in REMOTE" function is activated, the LED in the LOCAL/REMOTE key flashes.
All of the supplementary setpoints are deactivated for LOCAL master control.
After the master control has been transferred to the operator panel, none of the BICO
interconnections at bit 0 to bit 10 of the control word for the sequence control are active
(refer to function diagram 2501).
9.3.7.1
LOCAL/REMOTE key
Activation of LOCAL mode: Press the LOCAL key.
LOCAL mode: LED lights up
REMOTE mode: LED does not light up; the ON, OFF, JOG, direction reversal, faster, and
slower keys are not active.
Settings: Menu – Commissioning/Service – AOP settings – Control settings
Save LOCAL mode (factory setting: Yes)
● Yes: The "LOCAL" or "REMOTE" operating state is saved when the power supply is
switched off and restored when the power supply is switched back on.
● No: The "LOCAL" or "REMOTE" operating state is not saved. "REMOTE" is activated
when the power supply is switched on.
OFF in REMOTE (factory setting: No)
● Yes: The OFF key functions in REMOTE mode even if the drive is being controlled by
external sources (PROFIBUS, customer terminal strip, NAMUR terminal strip).
WARNING: This function is not an EMERGENCY STOP function.
● No: The OFF key only functions in LOCAL mode.
LOCAL/REMOTE also during operation (factory setting: No)
● Yes: You can switch between LOCAL and REMOTE when the drive is switched on (motor
is running).
● No: Before switching to LOCAL or REMOTE, a check is carried out to determine whether
the drive is in the "Operation" state. If it is, the system does not switch to
LOCAL/REMOTE and outputs the error message "LOCAL/REMOTE mode during
operation not possible".
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001