Commissioning
8.4 Commissioning with the STARTER commissioning tool
8.4.2.4
Connection through a serial interface
Along with the connection through the PROFIBUS, there is also a facility for data exchange
via a serial interface on the mainboard of the computer.
Note: The serial connection does not function with USB to serial converters.
Requirements
● A serial interface (COM) must be available on the PC from which the connection will be
made.
● An AOP30 must not be connected with the drive.
Connecting cables
Figure 8-32
Settings
1. Preparations on the device:
Make the following settings via the BOP20:
DO1.p0003 = 3
DO1.p2030 = 3
DO1.p2011 = 3 (left CUD) or
DO1.p2011 = 5 (right CUD)
The perform "Save parameters" and switch the electronic power supply OFF and ON
again so that the settings can take effect.
2. In STARTER, from Project > Set PG/PC interface, select the Serial cable (PPI) interface.
If this is not available in the drop-down list, you first have to add it using Select.
Note
If the interface cannot be added to the selection menu , the drive for the serial interface
still needs to be installed.
This is located in the following path on the STARTER CD:
\installation\starter\starter\Disk1\SerialCable_PPI\
STARTER must not be active while the driver is being installed.
298
Assignment, RS232 cable
ac.maher.co.ir
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001