Download Print this page

Siemens SINAMICS DCM Manual page 601

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Descriptions of functions
10.33 Diagnostics
CUD - Response of LEDs during ramp-up (following Power On)
Table 10- 58 Ramp-up
LED
RDY
DP1
Red
Red
Red 2 Hz
Red
Red 2 Hz
Red 2 Hz
Red
Orange
flashing
Red
Off
Off
Red
Red 0.5 Hz
Red 0.5 Hz
Orange
Off
Response of the LEDs after ramp-up
Table 10- 59 CUD - Description of the LEDs after ramp-up
LED
Color
RDY (READY) -
Green
Red
Orange
602
OPT
MOD
Off
Off
BIOS loaded
Off
Off
BIOS error
Off
Off
File error
Off
Off
Firmware loading
Off
Off
Firmware loaded
Off
Off
No CRC error
Off
Off
CRC error
Off
Off
Drive initialization
State
Description, cause
Off
Electronic power supply is missing or outside
permissible tolerance range.
Continuous
The component is ready for operation. No errors
light
are present.
0.5 Hz
Commissioning/reset
flashing
light
2 Hz flash-
Writing to memory card or internal flash memory
ing light
Notice!
The electronic power supply for the SINAMICS
DC MASTER must not be switched off during this
write process.
Switching off the electronic power supply can
lead to the loss of the parameter assignments.
Also refer to Chapter "Operation", Section
"Memory card functions".
2 Hz flash-
General errors
ing light
0.5 Hz
Updating the firmware of the connected DRIVE-
flashing
CLiQ components
light
2 Hz flash-
DRIVE-CLiQ component firmware update com-
ing light
plete. Wait for POWER ON for the respective
components.
ac.maher.co.ir
State
-
-
Memory card not present or
flash file system faulty
DP1 flashing without specific flashing
frequency
-
Firmware checked
Firmware checked, CRC error
-
Remedy
Check power supply
-
-
-
Check parameteriza-
tion/configuration
Carry out POWER ON for
the respective components
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Remark
SINAMICS DCM DC Converter

Advertisement