● Connectors with index: Parameter number, index, and drive object ID
● Data type (signal source for connector output parameter)
Figure 9-6
Note
A connector input (CI) cannot be interconnected with all connector outputs (CO, signal
source). The same applies to the binector input (BI) and binector output (BO).
For each CI and BI parameter, the parameter list shows the information on the data type of
the parameter and the data type of the BICO parameter under "data type".
For CO parameters and BO parameters, only the data type of the BICO parameter is shown.
Notation:
Data types BICO input: Data type parameter/Data type BICO parameter
Example: Unsigned32/Integer16
Data types BICO output: Data type BICO parameter
Example: FloatingPoint32
The possible interconnections between the BICO input (signal sink) and BICO output (signal
source) are listed in the table titled "Possible combinations for BICO interconnections", which
can be found in the "Explanations on the parameter list" section of the SINAMICS DCM List
Manual.
The BICO parameter interconnections can be implemented in different command data sets
(CDS). The different interconnections are activated by switching data sets. Drive object
interconnections are also possible.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Interconnecting signals using BICO technology
ac.maher.co.ir
Operation
9.1 Basic information
341