Download Print this page

Siemens SINAMICS DCM Manual page 393

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Descriptions of functions
10.3 Communication according to PROFIdrive
Overview of status words and actual values
Table 10- 12 Overview of status words and actual values, see function diagram [2450]
Abbreviation
Name
ZSW1
Status word 1
ZSW2
Status word 2
NACT_A
Speed setpoint A (16-bit)
G1_ZSW
Encoder 1 status word
G1_XIST1
Encoder 1 actual position value 1
G1_XIST2
Encoder 1 actual position value 2
G2_ZSW
Encoder 2 status word
G2_XIST1
Encoder 2 actual position value 1
G2_XIST2
Encoder 2 actual position value 2
E_DIGITAL
Digital input (16-bit)
IAIST_GLATT
Absolute actual current value, smoothed
MIST_GLATT
Actual torque value, smoothed
PIST_GLATT
Active power, smoothed
NACT_A_GLATT
Actual speed value, smoothed
MELD_NAMUR
VIK-NAMUR message bit bar
FAULT_CODE
Fault code
WARN_CODE
Alarm code
ZSW1_BM
Status word 1, variant for BM
ZSW2_BM
Status word 2, variant for BM
CU_ZSW1
Status word 1 for Control Unit
Data type according to PROFIdrive profile V4:
1)
I16 = Integer16, I32 = Integer32, U16 = Unsigned16, U32 = Unsigned32
ZSW1 (status word 1)
See function diagram 2452
Table 10- 13 Description of status word 1 (ZSW1)
Bit
Meaning
0
Ready for switching on
1
Ready for operation
394
Explanation
1
Ready for switching on
Power supply on, electronics initialized, line contactor
released if necessary, pulses inhibited
0
Not ready for switching on
1
Ready for operation
Line voltage applied, i.e. line contactor closed (if pre-
sent), field being built up
0
Not ready for operation
Reason: No ON command has been issued.
ac.maher.co.ir
Signal
Data type
number
2
U16
4
U16
6
I16
10
U16
11
U32
12
U32
14
U16
15
U32
16
U32
21
U16
51
I16
53
I16
54
I16
57
I16
58
U16
301
U16
303
U16
323
U16
325
U16
501
U16
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Interconnection
1)
parameter
r2089[0]
r2089[1]
r0063
r0481[0]
r0482[0]
r0483[0]
r0481[1]
r0482[1]
r0483[1]
r2089[2]
r0027
r0080
r0032
r0021
r3113
r2131
r2132
r2089[0]
r2089[1]
r2089[1]
Parameter
BO: r0899.0
BO: r0899.1

Advertisement