Connecting
6.1 Instructions for EMC-compliant drive installation
6.1.4
RFI suppression filter
Table 6- 1
Recommended RFI suppression filter from EPCOS
AC rated current
RFI suppression filter
Line filters for armature circuit
25 A
50 A
80 A
120 A
180 A
180 A
180 A
250 A
250 A
400 A
400 A
400 A
600 A
600 A
600 A
1000 A
1000 A
1000 A
1600 A
1600 A
1600 A
2500 A
2500 A
2500 A
Line filters for auxiliary power supply
25 A
50 A
66 A
90 A
120 A
Further information on the RFI suppression filters can be found on the Internet page of
EPCOS.
EPCOS (http://en.tdk.eu)
Radio interference suppression filters generate leakage currents. In accordance with
EN 61800-5-1, a PE connection with a cross-section of 10 mm
106
TN / TT supply systems
760/440 V
760/440 V
760/440 V
760/440 V
-
520/300 V
760/440 V
520/300 V
760/440 V
-
520/300 V
760/440 V
-
520/300 V
760/440 V
-
520/300 V
760/440 V
-
520/300 V
760/440 V
530/310 V
760/440 V
-
520/300 A
520/300 A
520/300 A
520/300 A
520/300 A
ac.maher.co.ir
IT system
580/335 V
580/335 V
630/365 V
630/365 V
690/400 V
360/208 V
560/320 V
360/208 V
560/320 V
690/400 V
360/208 V
560/320 V
690/400 V
360/208 V
560/320 V
690/400 V
360/208 V
560/320 V
690/400 V
360/208 V
560/320 V
460/265 V
560/320 V
690/400 V
440/255 A
440/255 A
440/255 A
440/255 A
440/255 A
2
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Article number
EPCOS
B84143A0025R021
B84143A0050R021
B84143A0080R021
B84143A0120R021
B84143B0180S024
B84143B0180S080
B84143B0180S081
B84143B0250S080
B84143B0250S081
B84143B0400S024
B84143B0400S080
B84143B0400S081
B84143B0600S024
B84143B0600S080
B84143B0600S081
B84143B1000S024
B84143B1000S080
B84143B1000S081
B84143B1600S024
B84143B1600S080
B84143B1600S081
B84143B2500S020
B84143B2500S021
B84143B2500S024
B84143A0025R105
B84143A0050R105
B84143A0066R105
B84143A0090R105
B84143A0120R105
is required.