Download Print this page

Siemens SINAMICS DCM Manual page 531

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Descriptions of functions
10.13 Speed controller
The following diagram shows the step response of the speed controller if the same controller
parameters are set as above, however, with the reference model activated.
r52174
r52167
Note
See Chapter "Commissioning", Section "Manual optimization" for the procedure to manually
optimize the speed controller
Use of the speed controller for other applications
If the SINAMICS DCM is not used for the speed control of a motor, but rather for the voltage
control of a capacitor load, it may be advantageous to support the speed controller working
as a voltage controller with a load connection. The "Load connection" function block is
available for this purpose. This function block is shown on function diagram 6851. It provides
an additional current setpoint that is preferably fed in at p50601[3] (see function diagram
6840).
532
Speed setpoint
Actual speed value
ac.maher.co.ir
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001