Operation
9.2 Parameterizing using the BOP20 (Basic Operator Panel 20)
9.2
Parameterizing using the BOP20 (Basic Operator Panel 20)
9.2.1
General information about the BOP20
The BOP20 can be used to power drives up and down during the commissioning phase as
well as display and modify parameters. Faults can be diagnosed as well as acknowledged.
Overview of displays and keys
Figure 9-9
Information on the displays
Table 9- 5
Displays
Display
Meaning
Top left
The active drive object of the BOP is displayed here.
2 digits
The displays and key operations always refer to this drive object.
RUN
Lights up if at least one drive in the drive line-up is in the RUN state (in operation).
RUN is also displayed via bit r0899.2 of the drive.
Top right
The following is displayed in this field:
2 digits
S
Lights up if at least one parameter was changed and the value has not yet been transferred to
the non-volatile memory.
P
Lights up if, for a parameter, the value only takes effect after the P key is pressed
C
Lights up if at least one parameter was changed and the calculation for consistent data man-
agement has still not been initiated.
Bottom 6 digits
Displays. parameters, indices, faults, and alarms, for example
344
Overview of displays and keys
More than 6 digits: Characters that are present but cannot be seen (e.g. "r2" ––> 2 charac-
ters to the right are invisible, "L1" ––> 1 character to the left is invisible)
Faults: Selects/displays other drives with faults
Designation of BICO inputs (bi, ci)
Designation of BICO outputs (bo, co)
Source object of a BICO interconnection with a drive object different than the active one
ac.maher.co.ir
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001