Operation
9.1 Basic information
9.1.5.3
Internal encoding of the binector/connector output parameters
Internal encoding is required for writing BICO input parameters via PROFIBUS, for example.
Figure 9-7
9.1.5.4
Example: Interconnecting digital signals
Suppose you want to operate a drive via terminals DI 0 and DI 3 on the CUD using jog 1 and
jog 2.
Figure 9-8
9.1.5.5
Information on BICO technology
Binector-connector converters and connector-binector converters
Binector-connector converters
● Several digital signals are converted to a 32-bit integer double word or to a 16-bit integer
word.
● p2080[0...15] BI: PROFIdrive PZD send bit-by-bit
342
Internal encoding of the binector/connector output parameters
Interconnecting digital signals (example)
ac.maher.co.ir
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001