Descriptions of functions
10.7 EtherNet/IP
10.7.2
Configuration of SINAMICS DCM for EtherNet/IP
10.7.2.1
Setting the IP address and activating the EtherNet/IP protocol
Requirements
● Version with option G00/G10 (Advanced CUD)
● MMC memory card with firmware version as of 1.4 to load the CBE20 firmware for
EtherNet/IP to the CBE20. The CBE20 firmware is installed as standard for PROFINET.
See also the information on the hardware/software compatibility in the preface.
● CBE20
The IP configuration is performed via STARTER or through direct parameter input via the
BOP or AOP30.
Table 10- 44 Settable parameters on the drive object CU
Parameter
p8941
p8943
p8942
p8940
p8945=2
In addition to direct input, the IP address can also be obtained via DHCP.
Configuration of EtherNet/IP on the drive unit
1. For setting the IP address directly via parameters, see above.
2. Activation of EtherNet/IP
– Insert the memory card with firmware version as of 1.4 into the appropriate slot of the
– Set access level 3 (p0003=3) in the drive object CU (BOP object 1) via STARTER,
– Activate the device configuration on the CU by setting p0009=1.
– Activate EtherNet/IP by setting p8835=4 on the CU.
– Complete the device configuration on the CU by setting p0009=0.
– Save the parameters (copy RAM to ROM).
– Switch the device off and on again.
– After power-up, the SINAMICS DC MASTER is visible as Ethernet/IP slave in the
498
IP address
Subnet screen
Default gateway
Name of station
Save and activate IP configura-
tion
CUD.
BOP or AOP30.
network.
ac.maher.co.ir
Note
Setting is mandatory
Setting is mandatory
-
In contrast to PROFINET, setting is not mandatory.
Setting must be made when the parameters are
entered directly.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001