When connecting temperature sensors with three wires, a jumper must be inserted between
X53x.2 and X53x.4.
Table 7- 42
Terminal
X531
X532
X533
X534
X535
X536
NOTICE
Motor damage due to incorrectly connected KTY temperature sensor
A KTY temperature sensor connected with incorrect polarity cannot detect if the motor
overheats. Overheating may result in damage to the motor.
• Connect a KTY temperature sensor with the correct polarity.
NOTICE
Overheating of the motor through jumpering the temperature sensor connections
Jumpering of the temperature sensor connections "+ Temp" and "- Temp" results in
incorrect measurement results. Damage to the motor can result if the overheating is not
detected.
• When using several temperature sensors, separately connect the individual sensors to
"+ Temp" and "- Temp".
NOTICE
Overheating of the motor through cables with too high a resistance
Cable length and cable cross-section can falsify the temperature measurement (10 Ω cable
resistance for a PT100 can falsify the measurement result by 10%). Damage to the motor
can result if the overheating is not detected.
• Use only cable lengths ≤ 300 m.
• For cable lengths >100 m, use cables with a cross-section of ≥1 mm
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Channel assignment
Channel number [x]
for 1x2, 3 and 4-wires
0
1
2
3
4
5
ac.maher.co.ir
Additional system components
7.5 Terminal Module TM150
Channel number [y]
for 2x2 wires
6
7
8
9
10
11
.
2
249

Advertisement

loading