Siemens SINAMICS DCM Manual page 268

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Maximum armature current < 0.5 × rated armature DC current for the device
The rated field DC current for the device must be adapted by setting p50076[1] (in %) if:
Maximum field current < 0.5 × rated field DC current for the device
Adapt to the actual device supply voltage
p50078[0]
p50078[1]
Acquiring the motor data
The motor data can be taken from the motor rating plate.
Figure 8-4
p50100[d]
p50101[d]
p50102[d]
p50103[d]
p50114[d]
When you have finished entering the motor data, choose "Continue" underneath the final
parameter value and activate with <F5> (OK).
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Rated input voltage for converter armature (in volts)
Rated input voltage for converter field (in volts)
Example of a rating plate
Rated armature current
Rated armature voltage
Rated excitation current
Minimum excitation current (optional)
Thermal time constant for motor
See the section titled "Thermal overload protection for the DC motor (I2t
monitoring of the motor)"
ac.maher.co.ir
8.3 Commissioning using the AOP30 operator panel
Commissioning
269